|
|
|
|
|
|
|
|
|
|
|
|
|||||||||||||||
![]() |
|
|
|||||||||||||||||||||||
|
|
|||||||||||||||||||||||||
|
|||||||||||||||||||||||||
|
|
|||||||||||||||||||||||||
|
|
|||||||||||||||||||||||||
|
|
|||||||||||||||||||||||||
|
|
|||||||||||||||||||||||||
|
|
Dumping and replacing the chemicals in a bath with a 12-hour lifetime, especially when semiconductor-grade chemicals with an environmental overhead are used, is costly. The deployment of multiple hoods and the need to perform nonproduction mixing steps multiply costs. Since water is a key component in wafer-surface preparation processes, it is reasonable to replace it after it evaporates. The utility of metering water back into the solvent is driven by cost and throughput. To replace spent water, DMOS5 asked the hood manufacturer to design a manual replenishing system that can drip water into the bath at selected rates. This redesign resulted in a supply line that was tied to the facility’s DI-water system and incorporated a pressure regulator, valve, and manual rotometer. The valve was controlled by software that permitted it to open at predetermined times (set by the engineer) and inject DI water through the rotometer. As shown in Figure 2, this continuous spiking system, when optimized, extended bath life from 12 to 48 hours. For all four baths at DMOS5, the new design resulted in a 75% cost savings.
The manual-replenishment system was closely monitored to ensure that control remained in the effective operating range. To accomplish that control, a solvent analyzer was installed to take samples of the solvent, analyze the solution, and provide a reading of water concentration once every 30 minutes, both on a display screen and a 4–20-mA analog output. The signal was integrated into the fab’s tool interdiction and monitoring system (TIMS), a fault detection and data collection system developed by Texas Instruments. Used to monitor equipment in real time and compare signals using a logic model programmed by the engineer, TIMS can take a series of predefined actions, such as initiating an alarm at the hood, shutting down a hood, paging a technician, or even sending e-mail alerts. Current Strategy: Replenishing DI Water at a Variable RateSet-rate-replenishment systems work reliably only under optimal operating conditions. Because such systems do not provide direct feedback from the analyzer to the hood, they do not account for concentration variability caused by process loadings, solvent drag-out, or tank replenishment. In addition, solvent mixture is not stable enough over time to increase bath life longer than 48 hours. After DMOS5 engineers had concluded that manual spiking control involved significant risks, an alternative method was pursued. Several different automatic direct-feedback methodologies to control water flow into the bath were considered, but because chemical concentration control can be challenging, the ideal instrument was difficult to find. An automatic control system that remains accurate under a variety of conditions was needed. Several criteria were evaluated: • Low Flow Control: DI water had to be metered into a heated solvent
tank at a low flow rate to compensate for evaporation. A metering valve
capable of controlling well at low flows was required. Automatic control
of such a valve necessitates an electronic flow measurement device
In addition to these requirements, the device had to be able to integrate
a flow controller with an automatic metering valve. The automatic replenishment
system and the flow controller had to work together to measure and adjust
flow automatically according to a variable setpoint. The integrated flow controller consists of three subcomponents: a differential-pressure flowmeter, a pro- portional control valve driven by a stepper motor, and proportional integral derivative control electronics. The unit receives a 0–10-V dc or 4–20-mA setpoint signal of the desired flow range and controls the proportional valve’s position to achieve the desired flow rate. Figure 4 shows a schematic diagram of the integrated system together with the concentration analyzer. A PLC was added to the system to determine the setpoint sent to the flow controller based on the concentration of water in the bath.
Using differential-pressure technology, the flowmeter in the integrated
flow controller determines flow by measuring fluid pressure before and
after an orifice in the flowmeter. The application flow rate and fluid
type determine the size of the orifice built into the flowmeter. As described
in Bernoulli’s principle, fluid flow passing through an orifice
increases in velocity, causing an increase in kinetic energy. The increase
in kinetic energy causes a corresponding loss of static energy, reflected
by a pressure drop across the orifice. An increase in flow causes a predictable
increase in differential pressure. Flow rate is proportional to the square
root of the pressure differential across the orifice, as shown in the
equation
Figure 5 presents a cross section of the flowmeter with differential-pressure technology. Additionally, the flowmeter provides analog signals for both flow and pressure measurement, triggering alarms for nonstandard processing conditions. The necessary flow range of DI-water replenishment was determined using the manual system. The integrated system was then mounted into a panel that included a display with a manual dial-in setpoint. A toggle switch was added to switch from the manual setpoint to the PLC setpoint. The PLC was programmed to give a varying output voltage to the integrated flow controller according to its input from the concentration analyzer. With that initial setting and historical readings from the analyzer, the right amount of DI-water flow was determined. Before the new system was installed, investigators confirmed that automatic control would be error-free. To do so, they filled a test bath with solvent and heated it to temperature. The concentration and set- point from the PLC were both interfaced to TIMS to collect data. After the system was set up, test wafers were processed to check drag-out and incoming DI-water pressure variability. Other tests were performed to check the bath for particles, trace metals, and contamination. The results of these tests did not deviate from the baseline. Initially, bath life was 48 hours; later, it increased to 72 hours, leading to even greater cost savings. ConclusionThe integrated flow controller with PLC feedback greatly improved the performance of the replenishment system. Figure 6 presents data from the solvent analyzer over a 72-hour period, and Figure 7 illustrates a graph of the TIMS historical viewer. The peaks in the graph show the concentrations of water after the bath has been freshly exchanged and automatic control has started following a short delay. The automatic replenishment system guarantees tighter control limits than the manual system and triggers an alarm through the TIMS system if the water concentration falls outside those limits. The integrated system allows for true loop feedback control in a critical application.
Texas Instruments improves manufacturing processes continually to provide
customers with the highest-quality electronic devices. Since low yields
and scrap are costly and affect customers negatively, the fab must be
able to exert strict control over all processes. The method detailed in
this article transformed solvent processing at DMOS5 from a process in
which there was no statistical control over water concentration to one
with consistent 6s capability. Greater stability has led to a sixfold
increase in solvent bath life, resulting in a sixfold increase in utilization
times and a >75% reduction in solvent costs. Additional benefits include
a reduction in engineering time and maintenance by approximately 5 hours
per week. AcknowledgmentsThe author would like to thank Evelyn Lafferty, a plasma process engineer at Texas Instruments, for her assistance and for helping to clarify some of the work discussed in this article. He would also like to acknowledge David Albrecht of Entegris Sensing and Control for his technical knowledge of flow instrumentation.
MicroHome |
Search | Current Issue | MicroArchives Questions/comments about MICRO Magazine? E-mail us at cheynman@gmail.com. © 2007 Tom Cheyney |
|
|
|
| |||||||||||||||||||